autotransformer : ウィキペディア英語版
autotransformer
An autotransformer (sometimes called ''autostep down transformer'')〔Paul Horowitz and Winfield Hill, ''The Art of Electronics Second Edition'', Cambridge University Press, Cambridge MA, 1989, ISBN 0-521-37095-7, page 58〕 is an electrical transformer with only one winding. The "auto" (Greek for "self") prefix refers to the single coil acting on itself and not to any kind of automatic mechanism. In an autotransformer, portions of the same winding act as both the primary and secondary sides of the transformer. In contrast, an ordinary transformer has separate primary and secondary windings which are not connected.
The winding has at least three taps where electrical connections are made. Since part of the winding does "double duty", autotransformers have the advantages of often being smaller, lighter, and cheaper than typical dual-winding transformers, but the disadvantage of not providing electrical isolation between primary and secondary circuits. Other advantages of autotransformers include lower leakage reactance, lower losses, lower excitation current, and increased KVA rating for a given size and mass.
Autotransformers are often used to step up or step down voltages in the 110-115-120 V range and voltages in the 220-230-240 V range - for example, providing 110 V or 120 V (with taps) from 230 V input, allowing equipment designed for 100 or 120 V to be used with a 230 V supply. This allows US electrical equipment to be fed from the higher European voltage. Autotransformers can also be used to supply European 230 V appliances from a 100 or 120 V supply in countries outside Europe. In all cases the supply and the autotransformer must be correctly rated to supply the required power.
==Operation==

An autotransformer has a single winding with two end terminals, and one or more terminals at intermediate tap points, or it is a transformer in which the primary and secondary coils have part of, or all of their turns in common. The primary voltage is applied across two of the terminals, and the secondary voltage taken from two terminals, almost always having one terminal in common with the primary voltage. The primary and secondary circuits therefore have a number of windings turns in common. Since the volts-per-turn is the same in both windings, each develops a voltage in proportion to its number of turns. In an autotransformer part of the current flows directly from the input to the output, and only part is transferred inductively, allowing a smaller, lighter, cheaper core to be used as well as requiring only a single winding.〔(Commercial site explaining why autotransformers are smaller )〕 However the voltage and current ratio of autotransformers can be formulated the same as other two-winding transformers:
\frac=\frac = a
(021)
The ampere-turns provided by the upper half:
F_U = (N_1 - N_2)I_1 = (1-\frac)N_1I_1
The ampere-turns provided by the lower half:
F_L = N_2(I_2 - I_1) = \frac(I_2-I_1)
For ampere-turn balance, FU=FL:
(1-\frac)N_1 I_1 = \frac(I_2-I_1)
Therefore:
\frac = \frac
One end of the winding is usually connected in common to both the voltage source and the electrical load. The other end of the source and load are connected to taps along the winding. Different taps on the winding correspond to different voltages, measured from the common end. In a step-down transformer the source is usually connected across the entire winding while the load is connected by a tap across only a portion of the winding. In a step-up transformer, conversely, the load is attached across the full winding while the source is connected to a tap across a portion of the winding.
As in a two-winding transformer, the ratio of secondary to primary voltages is equal to the ratio of the number of turns of the winding they connect to. For example, connecting the load between the middle and bottom of the autotransformer will reduce the voltage by 50%. Depending on the application, that portion of the winding used solely in the higher-voltage (lower current) portion may be wound with wire of a smaller gauge, though the entire winding is directly connected.
If one of the center-taps is used for the ground, then the autotransformer can be used as a balun to convert a balanced line (connected to the two end taps) to an unbalanced line (the side with the ground).

抄文引用元・出典: フリー百科事典『 ウィキペディア(Wikipedia)
ウィキペディアで「autotransformer」の詳細全文を読む